RF RC M30
Wireless magnetic sensor
- Thermoplastic or stainless steel enclosure
- Power supply: Lithium battery
- sWave® wireless technology
Applied standards | EN 60947-5-1, EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-31, EN ISO 13849-1, EN ISO 14119 |
---|---|
Enclosure | zinc die-cast, enamel finish |
Actuator | stainless steel 1.4301 |
Switch type | type 2 |
Coding level | low coding |
Degree of protection | IP 67 to IEC/EN 60529 |
B10d (10 % load) | 2 million |
TM | max. 20 years |
Switch insert | 1 x Ex 95 |
Contact material | silver |
Switching system | slow action, positive break NC contacts ![]() |
Switching elements | 1 NC/1 NO contact or 2 NC contacts, type Zb |
Connection | screw connection terminals |
Cable cross-section | max. 1.5 mm² (incl. conductor ferrules) |
Cable entry | 3 x M20 x 1.5 |
Clamping range | 7 … 12 mm |
Rated impulse withstand voltage Uimp | 4 kV |
Rated insulation voltage Ui | 250 V |
Conventional thermal current Ithe | 6 A |
Rated operating current/voltage Ie/Ue | 6 A/250 VAC; 0.25 A/230 VDC |
Utilisation category | AC-15; DC-13 |
Short-circuit protection | 6 A gG/gN fuse |
Positive break travel | 8.3 mm |
Ambient temperature | T6: –20 °C … +40 °C; T5: –20 °C … +60 °C |
Mechanical life | > 1 million operations |
Impact energy | max. 7 J |
Ex marking | ![]() ![]() T80 °C/T95 °C Db IECEx Ex db e IIC T6/T5 Gb, Ex tb IIIC T80 °C/T95 °C Db |
Approvals | BVS 04 ATEX E 126 IECEx BVS 07.0013 |