Safety relay module SRM 21 RT2

  • Enclosure width: 22.5 mm
  • 2 NC or 1 NC/1 NO contact can be connected
  • Feedback circuit
  • 2 enabling paths
  • 1 transistor output
  • Manual or automatic reset
  • LED indicator for switching condition
  • Crossed wire monitoring
  • N.B.: Please state required international approvals with your order!

Technical data

StandardsEN ISO 13849-1; EN 62061;
EN 60204-1, BG-GS-ET 20;
EN 60947-5-1, -3; EN 61326-3-1
Enclosureblack polycarbonate; polyamide terminal clamps V00, side parts PBT/PC Valox 357x, colza yellow
Contact materialAgNi 10 + 0.2 µm Au
MountingDIN rail mounting
Connectionscrew terminals with + and - screws
Cable cross-sectionmin. 1x 0.5 mm² (AWG 20) including conductor ferrules, max. 1x 2.5 mm² (AWG 14) including conductor ferrules, 2x 1.5 mm² (AWG 16) including conductor ferrules
Tightening torque0.8 Nm
Degree of protectionenclosure IP 40, terminal block IP 20 to IEC/EN 60529, protection against contact to VBG 4
 
Safety-relevant data:*
EN 60204-1stop category 0
EN 62061SIL CL 3
PFHd3 x 10-8 1/h
EN ISO 13849-1PL e, Category 4
TMmax. 20 years
MTTFd> 113 years
DC/DCavg> 99 %
 
Safety requirements nop
hop8 h/day
dop220 days/year
tzyklus30 s
 
Rated operating voltage Ue24 VDC ±15 %
Rated operating current Ie0.125 A
Rated operating isolation voltage Ui250 VAC
Rated impulse withstand voltage Uimp4 kV
Conditional short-circuit current100 A
Inputs1 NC/1 NO contact or 2 NC contacts, 1 feedback circuit, 1 start input (monitored)
Outputs2 enabling paths, 1 transistor output as signalling output
Ie/Ue to EN 60947-5-12 A/230 VAC; 1 A/24 VDC
Ithe to EN 60947-5-15 A
Utilisation categoryAC-15; DC-13
Ie/Ue to CSAB300/R300, 250 VAC
Contact load capacitymin. 10 mA
Typ. input current/
voltage
22 mA/ 20 VDC
Max. load of signalling output20 mA
Max. fuse ratingpower supply 2A slow blow, enabling paths 6 A gG/gN fuse
Delay on energisation/ deenergisation≤ 20 ms
Risk time≤ 0.5 s (switch-on delay)
Attendance delay tv< 200 ms
Mechanical life> 50 million operations
Display1 LED for supply voltage, 1 LED each for input A and B, 1 LED for authorisation
Degree of pollution2
Overvoltage categoryIII
Ambient temperature–22 °C … +55 °C
Storage and shipping temperature–22 °C … +70 °C
Relative humidity10 % ... 90 %
Shock resistance15 g
Approvals
on request
NoteInductive loads (contactors, relays etc.) are to be suppressed by suitable circuitry.

* The safety-related data are based on a load of 24 V / 1 A / DC-1 for the enabling paths.
With higher load currents for the enabling paths and other requirement rates nop, the safety-related data vary from the given data and can be provided on request.
Weight220 g

Ordering details

Type   Material no.  
Type    Material no.   
Safety relay module SRM 21 RT2 stock type Standard versions, in stock or available at short notice 1179203
Order now
If you cannot find the version you require, just ask us! Our product portfolio to date has included many customised switchgear variants.