ES 14 -40°C Extreme

  • Cold-resistant down to -40 °C
  • Thermoplastic enclosure
  • Double insulated
  • Mounting hole diameter 22.5 mm
  • Mounting details to EN 50047
  • With pre-wired cable, cable length 2 m
  • N.B.: Please state required international approvals with your order!

Technical data

StandardsEN ISO 13849-1; EN 60947-5-1
Enclosureglass-fibre reinforced, shock-proof thermoplastic (PA 66), self-extinguishing UL 94-V0
Degree of protectionIP 65 to IEC/EN 60529
Contact materialsilver
Switching systemslow action, positive break NC contacts
Switching elements2 NC contacts, type Zb
Connectioncable 4 x AWG 20
Cable cross-section4 x 0.56 mm²
B10d (10 % load)60 000
TMmax. 20 years
Uimp4 kV
Ui250 V
Ithe6 A
Ie/Ue6 A/250 VAC; 0.25 A/230 VDC
Utilisation categoryAC-15; DC-13
Max. fuse rating6 A gG/gN fuse
Ambient temperature–40 °C … +65 °C
Mechanical life> 30 000 operations
Operation cycles1800/h
Contact openingmax. 2 x 4 mm
Approvals

Ordering details

Emergency-stop push button QRUV

Type   Material no.  
Type    Material no.   
ES 14 QRUV 2Ö 2m -40°C...+65°C Extreme
1264315
If you cannot find the version you require, just ask us! Our product portfolio to date has included many customised switchgear variants.
If you cannot find the version you require, just ask us! Our product portfolio to date has included many customised switchgear variants.